Compressor Does Not Run
Unit Short Cycles
Contractors or Relays Burn Out
Start Capacitors Burned Out
Run Capacitors Burned Out
Unit Operates Long or Continuously
Box Temperature Too High
Discharge Pressure Too High
Discharge Pressure Too Low
Suction Pressure Too High
Suction Pressure Too Low
Noisy Unit
Compressor Loses Oil
Evaporator Fans Will Not Operate
Coil Does Not Clear Of Frost During Defrost
Ice Accumulating in Drain Pan
Ice Accumulating on Ceiling Around Evaporator and/or on Fans, Guards or Venturi

Walk in freezer and cooler home » Service » Training

Unit Short Cycles

Spacer image
Questions Cause Remedy
What is the thermostat differential setting? Control differential set too closely Widen differential
Have you checked condenser? Cycling on high pressure Clean dirty condenser. Check water supply on water-cooled condenser
Have you checked Discharge valve? Discharge valve leakin Correct condition
Have you checked the sight glass? Shortage of refrigerant Reclaim overcharge
  Refrigerant overcharge Reclaim overcharge
Have you checked the expansion valve? Leaky expansion valve. Replace
Is compressor hot? Compressor-motor overload cutting out Check for high head pressure, tight bearings, stuck pistons, clogged air or water-cooled condenser or water shut-off