Discharge Pressure Too High

Spacer image
Questions Cause Remedy
Is the condenser clean? Dirty condenser Clean condenser
Are the condenser fans running? Condenser fans not running Repair or replace
Is the water valve open? Water shut off Turn on water
  Water-cooled condenser restricted Clean or replace condenser
Have you checked the refrigerant charge? Refrigerant overcharge Recover excess charge
Is there air or other non-condensables in the system? Non-condensables in the system Remove from the system
Where is the unit located? What is air temperature entering condenser? Poorly ventilated or hot location Properly ventilate unit or relocate
Is there any air recirculation from this or any other units? Air recirculation Properly ventilate unit or relocate
Is discharge valve partially closed? Discharge valve partially closed Open discharge valve
Is heat pressure control set and functioning properly? Head pressure setting too high. Headmaster malfunctioning Adjust setting or replace control