Discharge Pressure Too Low

Spacer image
Questions Cause Remedy
Where is the unit located? What is air temperature entering condenser? Cold ambient air temperature or cold water. None. Efficiency increased.
Have you checked refrigerant charge? Refrigerant shortage. Repair leak and recharge.
Is compressor suction or discharge valve partially closed? Compressor suction or discharge valve partially closed. Open valve.
Is compressor suction or discharge valve leaking? Compressor suction or discharge valve inefficient. Clean or replace leaky valve plates.
Is condenser pressure regulator operating properly? Faulty condenser pressure regulator. Repair or replace.
Do you have low suction pressure? See section XI on low suction pressure. Correct.