Walk in freezer and cooler home » Service » Training

Suction Pressure Too High

Spacer image
Questions Cause Remedy
Are suction lines insulated properly? i.e. from outside of box to compressor. (Hot weather) Suction lines improperly or not insulated Insulate suction lines
Do you have the correct expansion valve? Oversized expansion valve Replace with properly sized expansion valve
Where is expansion valve bulb located? Expansion valve bulb in improper location Move expansion valve bulb
Is expansion valve bulb insulated? Expansion valve bulb improperly or not insulated Insulate expansion valve bulb properly
Is expansion valve in proper adjustment? Expansion valve overfeeding Adjust expansion valve until proper superheat is reached
Is system capacity sufficient for product load? Product load greater than system capacity Add additional units or replace